Impedance tolerance raises the available fault current

zTol 0.9 (−10% Z) is the worse-case available current choice in the product engine.

Fault Current & SCCR Label

Multiplier = 100 / (%Z × zTol). Lower effective %Z means a higher multiplier and higher Isc at the transformer terminals before feeder reduction.

Product vectors show the same 1500 kVA / 480 V / 3.5%Z case rising from about 51.6 kA without tolerance to about 57.3 kA with zTol 0.9.