- Read the nameplate: kVA, secondary voltage, %Z.
- Choose source modeling: infinite bus, or primary/secondary utility current from a letter when you have it.
- Optional tolerance: −10% Z (zTol 0.9) raises available current for a worse-case look.
- First feeder: length, conductors, raceway, parallels reduce current at the next point.
Example shape from product vectors (not a substitute for your inputs): 1500 kVA, 480 V, 3.5%Z without tolerance is on the order of 51.5 kA at the terminals before feeder reduction.
Related: tolerance boost · utility letter / known node · full method.