The method family used by the product. Not a substitute for a stamped short-circuit study.

Fault Current & SCCR Label

Point-to-point starts at the transformer, then applies a multiplier from percent impedance, then reduces current along each feeder using length, voltage, parallels, and a conductor C value.

At the transformer

  1. Full-load amperes from kVA and secondary voltage (three-phase or single-phase formulas in the product engine).
  2. Multiplier = 100 / (%Z × zTol). Use zTol 0.9 when you apply a −10% impedance tolerance for worse-case available current; 1.0 with no tolerance.
  3. Isc at transformer terminals = FLA × multiplier. Optional motor contribution adds at the terminals when enabled (Pro).

Along the feeder

  1. Compute factor f from length, starting current, C, parallels, and voltage.
  2. M = 1 / (1 + f).
  3. Isc at the point = starting current × M.

C values come from the published table used by the engine (copper/aluminum, steel/nonmagnetic raceway, sizes through large kcmil). Wrong C breaks every downstream point.

Calculation and label are a field aid, not an engineering stamp or local-code guarantee.